The NEC tap rule is really just a set of common-sense exceptions to a fundamental electrical safety rule. Found in NEC 240.21, it lets you connect a smaller wire—the "tap conductor"—to a much larger circuit without putting a circuit breaker right at the connection point. It’s a solution born from real-world necessity, especially in industrial settings where adding a breaker at the tap is often completely impractical.
So, Why Do We Even Need a Tap Rule?
The National Electrical Code is built on one core safety principle: protect a wire from overcurrent right where it gets its power. Simple enough. This usually means every time you go from a big wire to a smaller one, you need a fuse or breaker in between. But what happens when that's just not possible?
Picture a massive, high-amperage busway running along the ceiling of a packaging plant. You need to drop power down to a single control panel or motor starter on the floor. Sticking a bulky overcurrent device way up on the busway for that one small connection would be a nightmare to install and maintain.
This is where the tap rule comes in. It’s not a free-for-all loophole; it’s a carefully engineered set of guidelines that acknowledges a short, protected run of wire is extremely unlikely to fail. Think of it less like breaking the rules and more like a controlled, pre-approved detour.
The logic is sound. The NEC allows this exception because it builds in several non-negotiable safety layers:
- Keep It Short: The length of the unprotected tap wire is strictly limited—usually to 10 feet or 25 feet—to drastically reduce the exposure to physical damage or a potential fault.
- Size It Right: The tap wire can't be just any size. It has to be beefy enough to handle the potential fault current until the downstream breaker (the one at the end of the tap) has a chance to trip.
- Protect It Physically: Tap conductors can't just be left dangling. They absolutely must be installed inside a raceway, like a rigid metal conduit, to shield them from getting crushed, cut, or damaged.
At the end of the day, understanding the tap rule is all about knowing how to safely tie into an existing electrical system. While it's a specific electrical concept, you can see similar logic in other fields—for a different perspective on making live connections, you might find it interesting to read about the general concept of hot tapping in pipeline repair.
By sticking to these precise guidelines, we can build electrical systems that are both highly functional for the plant floor and fully compliant with the highest safety standards, preventing fires and protecting our equipment.
NEC Feeder Tap Rules at a Glance
To make sense of the different scenarios, it helps to see the most common feeder tap rules laid out side-by-side. This table gives you a quick snapshot of the length limits and core requirements for each.
| Tap Rule | Maximum Length | Minimum Ampacity Requirement | Termination Device |
|---|---|---|---|
| 10-Foot Tap Rule | 10 feet | Must be at least the ampacity of the load served and the rating of the termination device. | Must terminate in a single circuit breaker, a set of fuses, or an approved overcurrent protective device. |
| 25-Foot Tap Rule | 25 feet | Must be at least 1/3 the ampacity of the feeder's overcurrent device. | Must terminate in a single circuit breaker or a set of fuses rated no more than the tap conductor's ampacity. |
| Outside Tap Rule | Unlimited | Sized for the calculated load, following standard conductor sizing rules. | Must terminate in a readily accessible overcurrent device located near the point of entrance. |
| Transformer Taps | Per NEC 240.21(C) | Varies based on primary/secondary protection and specific rule subsection. | Typically terminates in an overcurrent device on the secondary side. |
Think of this table as your cheat sheet. While the full code text has all the nuances, these are the big-picture requirements you'll encounter most often when designing or inspecting an installation.
Getting to Know the Three Main Feeder Tap Rules
While the general idea of the NEC tap rule gives us a starting point, its real-world use is all about a few specific, common-sense exceptions. These rules aren’t interchangeable—not by a long shot. Each one is built for a different scenario, with its own strict recipe for length, conductor size, and how you terminate the run. Figuring out which rule fits your job is the first step to a safe, compliant installation.
At its core, the reason we even have these rules is simple: electrical protection. This flowchart really boils it down to the first question you should ask: if a conductor has overcurrent protection right where it starts, it's a standard, protected circuit. If not, you’re officially in tap rule territory.

This visual guide cuts through the noise. The second you see there's no Overcurrent Protection Device (OCPD) at the tap point, your only path forward is to follow one of the specific NEC tap rules to the letter.
The 10-Foot Tap Rule
This is the one you’ll see most often, which is why it’s often just called the "short tap." The rule, found in NEC 240.21(B)(1), is perfect for those tight spots where equipment is right next to the feeder. Think tapping a busway to feed a disconnect directly below it, or powering a small control transformer inside a larger panel.
The logic here is pretty straightforward: a very short run of wire, completely enclosed in a protective raceway, has an incredibly low chance of getting damaged and causing a problem. But that flexibility comes with some very firm conditions.
To use the 10-foot tap rule, you have to check every single one of these boxes:
- Length: The tap conductors can't be a hair over 10 feet long.
- Ampacity: The wire's ampacity must be at least the calculated load it serves and be equal to or greater than the rating of the device it lands on.
- Protection: The conductors have to be installed in a raceway to shield them from physical damage.
- Termination: This is the big one. The tap conductors must terminate in a single circuit breaker or a single set of fuses.
Key Takeaway: The 10-foot rule is a strict exception that absolutely does not let you feed a lighting panel or a distribution panelboard directly. That requirement for termination on a single overcurrent device is non-negotiable.
The 25-Foot Tap Rule
When you need to cover a bit more ground, the 25-foot tap rule in NEC 240.21(B)(2) gives you more length. But in exchange, it demands a beefier conductor to make up for the added risk. You’ll see this rule a lot in industrial plants for hooking up machinery that isn't parked right next to the main power source.
Because the wire run is longer, the NEC forces you to upsize the conductor. This ensures it can handle a potential fault current from the main feeder's breaker without melting down before the breaker can trip.
Here’s the checklist for this rule:
- Length: The total length of the tap conductor must not exceed 25 feet.
- Ampacity: The tap conductor must have an ampacity of at least one-third (1/3) of the rating of the breaker or fuse protecting the main feeder.
- Protection: Just like the 10-foot rule, these wires must be enclosed in a raceway. No exceptions.
- Termination: The tap has to terminate in a single circuit breaker or set of fuses rated no higher than the tap conductor's ampacity.
That "one-third" sizing rule is a critical safety factor. For instance, if you're tapping a feeder that's protected by a 600A breaker, your 25-foot tap conductors need an ampacity of at least 200A (600A / 3).
The Over 25-Foot Tap Rule for High-Bay Buildings
This one is less common but absolutely essential in the right setting. The "Over 25-Foot" rule in NEC 240.21(B)(4) is the go-to for high-bay manufacturing facilities and other industrial buildings with soaring ceilings. It allows for taps up to a whopping 100 feet long, but it’s extremely restrictive and only applies under very specific circumstances.
This rule was written to solve a real-world problem: how do you safely tap an overhead busway in a building with a ceiling over 35 feet high and get power down to equipment on the floor?
The conditions are, as you'd expect, very stringent:
- Building Type: This is only allowed in high-bay manufacturing buildings where the ceiling height is over 35 feet.
- Length Limit: The total length of the tap can't exceed 100 feet.
- Installation: The conductors must be installed and maintained only by qualified persons.
- Ampacity: Same as the 25-foot rule, the ampacity has to be at least 1/3 of the feeder's overcurrent protection rating.
- Conductor Type: The tap conductors can't be smaller than 6 AWG copper or 4 AWG aluminum.
- Physical Protection: They must be in a raceway and can't be run where they could get damaged.
This specialized NEC tap rule is a perfect example of the code evolving to meet the needs of modern industrial environments, offering an engineered, safe solution for a unique challenge.
The Golden Rules for All Tap Conductors
Getting the math right on the 10-foot or 25-foot rules is only half the battle. Before you even think about lengths and ampacities, the NEC lays down a few non-negotiable ground rules. These principles apply to every single tap installation, no matter what.
Think of them as the fundamental safety backstops. They’re designed to prevent dangerous setups and are often the first things an inspector will look for. Getting these wrong is a surefire way to get a red tag, because they cut right to the core of electrical safety.
The No Daisy-Chaining Rule
Here’s the big one, and it's a mistake we see all too often: a tap conductor can never be tapped again. Seriously, don't do it. A tap is supposed to be a short, protected bridge from a high-capacity feeder to a single point of protection.
When you tap that tap, you create a daisy chain of unprotected wiring. This "tap on a tap" effectively creates a new branch circuit with no properly sized overcurrent protection device (OCPD) at its source, making it a massive fire hazard. The NEC is black and white on this: the tap's journey ends at one—and only one—protective device.
Your Taps Need Armor (Mandatory Physical Protection)
By their very nature, tap conductors aren’t protected by a breaker or fuse right where they begin. This leaves them incredibly vulnerable. If something damages the insulation and the wire shorts out, the only thing that can stop the runaway current is the massive upstream breaker on the main feeder. That can let a huge amount of fault current flow, which is a recipe for disaster.
To counter this risk, the NEC demands that all tap conductors be installed inside a raceway or a suitable enclosure. This isn't just a suggestion.
- Enclosed and Shielded: The wires must be protected from physical harm along their entire run. This typically means putting them in rigid metal conduit, EMT, or another approved raceway.
- No Exposed Wires: You can't just leave tap conductors hanging in the open, even for a few inches. The raceway is their suit of armor, guarding against cuts, crushing, and abrasion that could lead to a catastrophic failure.
One Tap, One Destination
Another universal rule is that every feeder tap must terminate at a single overcurrent protective device (OCPD). This means the tap has to land on the line-side lugs of a single circuit breaker or a single set of fuses.
Pay close attention to this: You cannot run a tap conductor straight to the main lugs of a panelboard and then feed multiple smaller breakers from there. The tap must feed a single main breaker that, in turn, protects the entire panelboard. This creates one clear point of disconnect for everything downstream.
Knowing what a proper OCPD looks like is key. If you want to see how these devices act as the final gatekeeper for a tap installation, you can learn more about an ABB circuit breaker and its role in the system. This single-device rule is a cornerstone of tap safety, preventing a single tap from spawning multiple, unprotected circuits.
Alright, let's get this done. The theory behind the NEC tap rule is one thing, but making it work on a noisy, chaotic plant floor is a completely different ballgame. This is where the codebook hits the concrete.
Let’s walk through two super common scenarios you’ll run into, breaking them down to show how these rules translate into safe, compliant, and practical installations.

These examples aren't just academic—they're the real-world calculations and gut checks you'll be making on the job.
Example 1: The 25-Foot Tap for a New Conveyor
Picture this: you're installing a new conveyor system in a packaging facility. It needs a 150A feed, and the most convenient power source is a 600A busway running along the ceiling, about 20 feet from the machine. Tapping right into the busway with a breaker is a non-starter. This is a textbook case for the 25-foot tap rule.
The plan is to tap the 600A busway and run conductors down to a 150A fused disconnect mounted on the wall right next to the new machine.
Here's how we'd tackle it, step-by-step:
- Pick Your Rule: The total run is 20 feet. That's more than 10 feet but less than 25 feet, so we know we're working with the 25-foot tap rule found in NEC 240.21(B)(2).
- Size the Conductor: This is the most critical calculation. The rule mandates that the tap conductor's ampacity must be at least one-third (1/3) the rating of the feeder's protection—in this case, the 600A busway. The math is straightforward: 600A / 3 = 200A. Our tap conductors need to be rated for at least 200A.
- Grab the Right Wire: Time to hit the ampacity tables. Looking at Table 310.16 (using 75°C terminations), we find that a 3/0 AWG THHN copper conductor is rated for exactly 200A. Perfect. It meets our minimum requirement.
- Check the Termination: The tap has to end at a single overcurrent protective device (OCPD). Our 150A fused disconnect fits the bill. Just as important, the 150A rating of the disconnect is less than the 200A ampacity of our 3/0 AWG tap wire. That's a key safety check you can't skip.
- Protect the Run: That entire 20-foot run of 3/0 wire can't just be hanging out. It absolutely must be installed inside a raceway, like rigid metal conduit, to shield it from physical damage.
Follow those steps, and you've got a rock-solid, fully compliant installation. The conductors are sized right, physically protected, and terminate correctly.
Example 2: The 10-Foot Tap in a Control Panel
Now for a smaller, more common job inside an existing control cabinet. We're adding a new PLC that needs a dedicated 120V source, so we have to drop in a small control power transformer (CPT). The panel's main bus is fed from a 225A breaker.
The CPT will be mounted just a couple of feet from the bus, all within the same enclosure. This is the ideal spot to use the 10-foot tap rule, NEC 240.21(B)(1).
A Quick Note on Enclosures: The NEC treats the inside of a control panel or wireway as a protected space. If you need a refresher on picking the right box for the job, you can explore the different electrical boxes types and what they're designed for.
Here’s the breakdown for the 10-foot rule:
- Confirm the Rule: The CPT is 3 feet from the bus—well under the 10-foot limit. We're good to go.
- Check Ampacity: The 10-foot rule is a bit different. The tap conductor must be rated for the greater of the load it serves or the rating of the device it terminates into.
- Pick Your Protection: We’ll protect the primary side of the CPT with a small, fused switch rated for 2A. This means our tap conductor needs an ampacity of at least 2A. A simple 14 AWG THHN copper wire, rated for 15A, is more than enough.
- Verify the Termination: The tap conductors run straight from the main bus to the line side of that 2A fused switch. That single set of fuses satisfies the rule’s requirement for terminating in a single OCPD.
- Ensure Protection: Since the entire tap is inside the metal control cabinet, the conductors are already considered protected from physical damage. No extra conduit is needed.
This is a classic example of why the 10-foot NEC tap rule is so useful. It lets you make small, essential power connections inside a panel without burning a valuable breaker slot for a tiny load. It's an efficient, safe solution you’ll see in control panels every single day.
Specialized Tap Rules for Transformers and Motors
The standard feeder tap rules handle a lot of common situations, but once you step onto the plant floor, things get more complicated. Industrial settings are packed with specialized equipment—transformers and motors, specifically—that have their own unique electrical personalities.
The National Electrical Code gets this. That's why it provides a distinct set of tap rules just for these applications. They aren’t completely new rules, but rather smarter, more specific versions of the feeder tap rules, adapted for the realities of inductive loads.
Getting these specialized rules right is non-negotiable for any plant engineer or packager. If you mistakenly apply a standard feeder rule to a transformer secondary or a motor circuit, you're asking for trouble. You could end up with improper protection, constant nuisance tripping, or even a catastrophic failure. The Code lays out these separate guidelines to account for things like massive transformer inrush current and the brutal startup demands of a motor.
Transformer Secondary Tap Rules
Transformers are the backbone of any plant's power distribution, stepping voltage up or down wherever you need it. The conductors coming off the secondary side of a transformer play by their own set of rules, which you'll find in NEC 240.21(C). It helps to think of a transformer secondary as creating a "separately derived system." It's essentially a new starting point for power, and your overcurrent protection has to reflect that.
The rules for transformer secondaries will feel familiar if you know the feeder tap rules, but the details are what matter. They allow for very specific lengths of unprotected conductor on the secondary side before an overcurrent protective device (OCPD) is required.
Here are the two scenarios you'll run into 99% of the time:
- The 10-Foot Secondary Rule: Just like the feeder tap rule, you can have up to 10 feet of unprotected secondary conductors. The key is that they must be properly sized for the load and must terminate in a single OCPD. You see this all the time when a disconnect is mounted right next to the transformer.
- The 25-Foot Secondary Rule: This rule gives you more breathing room, allowing up to 25 feet of secondary conductor. But there are strings attached: the conductors have to be sized with an ampacity of at least 1/3 of the transformer secondary rating, be physically protected inside a raceway, and terminate in a single OCPD.
The Big Picture: The whole point of these rules is to give you a practical way to get power from the transformer’s secondary lugs to the first line of defense—the breaker or fuse. The strict length limits and physical protection requirements make the risk of a fault on that short, unprotected run incredibly low.
Navigating Motor Circuit Tap Rules
This is where things can get really tricky. Motor circuits force you to juggle two different parts of the NEC: Article 240 (Overcurrent Protection) and Article 430 (Motors, Motor Circuits, and Controllers). This crossover is a massive source of confusion and failed inspections.
When you tap a feeder to supply a motor, you're still following the basic principles of the feeder tap rule. The difference is that the final termination requirements are dictated by the unique needs of the motor. Your tap has to end at the motor’s branch-circuit protective device, which is usually a fused disconnect or a special motor circuit protector inside a motor control center (MCC) bucket.
Think about tapping a busway to feed an individual motor starter. It requires careful coordination. The tap conductors themselves must be sized based on the appropriate NEC tap rule (like the 25-foot rule). However, the fuses or breaker at the end of that tap must be sized according to Article 430 to handle the motor's huge inrush current on startup.
This is a critical distinction. It ensures the motor can roar to life without instantly tripping the breaker, while still giving you the short-circuit protection you need. To make sure your designs are bulletproof, you can take a deeper dive into the specific requirements for the protection of motors in our detailed guide. Mastering these specialized rules is essential for keeping your most vital plant assets running safely and efficiently.
Common Tap Rule Violations and How to Avoid Them
Knowing the NEC tap rule is one thing. Actually avoiding the common slip-ups that get you a red tag from an inspector? That’s what really counts on the job site. Even seasoned installers can make simple mistakes that compromise safety and force expensive rework. Getting these rules right is a huge part of avoiding the common electrical problems home inspectors uncover and just doing a safe, professional job.
The best way to pass inspection is to think like an inspector. These violations aren't just about checking a box in the codebook; they represent very real fire and shock hazards that put people and equipment in jeopardy.

Mistake 1: Tapping a Tap
This is one of the most dangerous and, unfortunately, frequent violations I see. It’s simple: a tap conductor is meant to go from a protected feeder to a single overcurrent protective device (OCPD). Tapping that conductor again creates a daisy chain of unprotected wiring.
Think about it. You’re essentially creating a brand-new branch circuit that has no properly sized protection at its origin. If a fault happens on that second tap, the only thing that can clear it is the massive upstream breaker—which will happily let a dangerous amount of current flow long enough to start a fire.
The Fix: Treat every tap conductor like a one-way street. Its journey has to end at a single breaker or a set of fuses. If you need to power another piece of equipment, you have to go back to the original feeder or, better yet, install a small distribution panel fed from the first tap’s OCPD.
Mistake 2: Exceeding Length Limits
Those length limits—10 feet and 25 feet for the most common rules—aren't suggestions. They are hard-and-fast limits based on an accepted level of risk. A classic mistake is grabbing a tape measure and getting the straight-line distance, completely forgetting about the actual conductor length, which includes all the bends and turns inside the conduit.
Stretching that length increases the conductor's exposure to physical damage and voltage drop. More critically, it extends the run of wire that isn't immediately protected by a right-sized OCPD, which is the exact risk the tap rule is designed to manage.
Mistake 3: Botching the Ampacity Calculation
Getting the ampacity of a tap conductor wrong is another critical error. It usually happens in one of two ways:
- For the 25-foot rule, the tap conductor’s ampacity must be at least one-third of the feeder’s OCPD rating. It’s based on the breaker, not the feeder conductor's ampacity. Using the wire size as your reference is a fast track to an undersized tap.
- For the 10-foot rule, the tap has to be sized for the load it serves and the rating of the device it terminates on. In the rush of a job, this sometimes gets overlooked.
An undersized tap can't handle a fault. During a short circuit, it can overheat and melt long before that big upstream breaker even thinks about tripping. The entire protection scheme becomes useless.
To keep these common headaches off your punch list, run through a simple mental checklist before you pull any wire:
- Check the Source: Are you tapping a feeder or another tap? Make sure it's the feeder.
- Measure the Real Length: Pull a string or use a fish tape to measure the actual path the wire will take.
- Calculate Ampacity Right: Always base that 1/3 calculation on the feeder’s breaker, not its wire gauge.
- Confirm the Landing Spot: Does the tap land on a single OCPD? It has to.
- Look at Physical Protection: Is the entire tap run buttoned up in a raceway? No exceptions.
Frequently Asked Questions About the NEC Tap Rule
Even when you feel you've got a handle on the rules, weird situations always pop up on the job site. Let's walk through some of the most common questions about the NEC tap rule to bridge that gap between what the codebook says and what you actually see in the field.
Can I Feed a Small Subpanel with the 10-Foot Tap Rule?
This is probably the number one mistake we see people make, and the short answer is no.
The language in NEC 240.21(B)(1) couldn't be clearer: tap conductors have to terminate in a single circuit breaker or a single set of fuses. A subpanel, by definition, is a collection of multiple breakers, so landing your tap conductors directly on its main lugs is a serious violation.
Think of it this way: the tap is an intentional, limited exception to the rule. The only way the code allows it is if that unprotected run ends immediately at a single, dedicated shut-off. The correct way to do this is to run your tap conductors to one main breaker, which then protects the entire subpanel downstream.
For the 25-Foot Rule, Do I Size the Tap Wire to the Feeder Wire or the Breaker?
Another absolutely critical point. The one-third (1/3) ampacity requirement for the 25-foot tap is based on the rating of the overcurrent protective device (OCPD) that's protecting the main feeder. It has nothing to do with the size or ampacity of the feeder wires themselves.
For example, if you have a feeder protected by a 400A breaker, your tap conductors must have an ampacity of at least 133A (400A / 3). This is all about ensuring the smaller tap wire can survive a major fault long enough for that big upstream breaker to do its job and trip.
Are Tap Rules Common in Residential Wiring?
Not really. While the NEC is the law of the land for all electrical work, you'll almost exclusively run into tap rule scenarios in commercial and industrial settings.
Residential systems are just built on a different scale. Circuits are smaller, simpler, and almost always run directly from a dedicated breaker back at the main panel. The massive feeders, busways, and distribution switchboards that make the NEC tap rule a necessity are just not part of a typical home's construction.
At E & I Sales, we live and breathe this stuff. Our job is translating complex code into industrial solutions that are practical, reliable, and safe. Whether you need a custom UL-listed control panel or just some expert advice on a tricky motor control setup, our team has the hands-on experience to get your project done right. See how we can help with your next installation at https://eandisales.com.